BioCel M-Pak

  • Space-saving design reduces storage and handling cost
  • 149 mm depth filter with the same performance as 292 mm depth filters
  •  Sturdy high impact polystyrene cell sides enclose a fixed media pack
  • Fully incinerable
Share this:
Description

High Efficiency – Low Resistance

Rated 95% on 0.3 μm particles, and a MERV 16 per ASHRAE Standard 52.2, BioCel M-Pak filters have the advantage of a much lower pressure drop than a typical HEPA filter (0.36″ versus 1.0 in. w.g. at 250 FPM). BioCel M-Pak filters fill the gap between ASHRAE-grade high-efficiency filters and ultra-high-efficiency HEPAs, at a much lower weight and pressure drop.

This compact, lightweight filter will withstand operating temperatures to 176°F/80°C, if recommended final resistance is not exceeded. To maximize service life, use BioCel M-Pak filters with high quality AAF Flanders prefilters.

Cost-Saving Design

Due to the smaller footprint of the BioCel M-Pak filter, less space is required for storage. M-Pak filters are approximately 50% lighter than conventional 12″-deep filters that have metal cell sides. Easy handling means reduced maintenance costs and time savings. Disposal costs are also reduced, as two M-Pak filters can be disposed of in the space of one 12″-deep filter.

Construction

The header and cell sides of the BioCel M-Pak filter are constructed of high-impact polystyrene. The design, which encloses a fixed media pack, creates a rugged filter that resists damage during shipping, handling, and operation. All components of the BioCel M-Pak are fully incinerable.

Applications

The BioCel M-Pak filter is designed primarily to remove airborne biological contaminants in hospital-critical areas, and food and pharmaceutical processing plants. The filter is engineered to meet the exacting requirements of precision manufacturing operations and laboratories, where very high-efficiency filtration of fine particulate matter is necessary.

EN1822 E10
Filter Depth (mm) 149
Media Type Fiberglass
Frame Material Plastic
Separator Style Hot Melt
Special Size Available No
Antimicrobial Available No
Header Type Single Header
Gasket Material (Standard) None
Gasket Material (Optional) Neoprene, PU
Recomm. Final Resistance 500 Pa
Max. Operating Temperature 70˚C
Air Filtration Certificate UL 900

Subscribe to Our Latest Updates

  • Let us reach out to you

    AAF Asia is committed to protecting and respecting your privacy, and we’ll only use your personal information to administer your account and to provide the products and services you requested from us. From time to time, we would like to contact you about our products and services, as well as other content that may be of interest to you. By clicking submit below, you consent to allow AAF Asia to store and process the personal information submitted above to provide you the content requested.

     

  • Let us reach out to you

    AAF Asia is committed to protecting and respecting your privacy, and we’ll only use your personal information to administer your account and to provide the products and services you requested from us. From time to time, we would like to contact you about our products and services, as well as other content that may be of interest to you. By clicking submit below, you consent to allow AAF Asia to store and process the personal information submitted above to provide you the content requested.